EATON 259081 3x40A 50kA Kompakt Şalter
Marka: Eaton
Orijinal fiyat: 9.103,62₺.3.186,27₺Şu andaki fiyat: 3.186,27₺.
10.000₺ ve üzeri alışverişlerinize özel teklif.
EATON 259081 NZMN1-A40 3x40A 50kA Kompakt Şalter (Ayarlanabilir termik-manyetik korumalı)
Datasheet – NZMN1-A40 | ||||
Part no. | NZMN1-A40 | |||
Article no. | 259081 | |||
Catalog No. | 259081 | |||
1230PIC-785 | ||||
Similar to illustration | ||||
Delivery program | ||||
Product range | Circuit-breaker | |||
Protective function | System and cable protection | |||
Standard/Approval | IEC | |||
Installation type | Fixed | |||
Release system | Thermomagnetic release | |||
Construction size | NZM1 | |||
Number of poles | 3 pole | |||
Standard equipment | Box terminal | |||
Switching capacity | ||||
400/415 V 50 Hz | Icu | kA | 50 | |
Rated current = rated uninterrupted current | ||||
Rated current = rated uninterrupted current | In = Iu | A | 40 | |
Setting range | ||||
Overload trip | ||||
Ir | A | 32 – 40 | ||
Short-circuit releases | ||||
Non-delayed | Ii = In x … | 8 – 10 | ||
Short-circuit releases | Irm | A | 320 – 400 | |
Technical data | ||||
General | ||||
Standards | IEC/EN 60947 | |||
Protection against direct contact | Finger and back of hand proof to VDE 0106 Part 100 | |||
Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 | |||
Ambient temperature | ||||
Ambient temperature, storage | °C | – 40 – + 70 | ||
Operation | °C | -25 – +70 | ||
Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC 60068-2-27 | g | 20 (half-sinusoidal shock 20 ms) | ||
Safe isolation to EN 61140 | ||||
Between auxiliary contacts and main contacts | V AC | 500 | ||
between the auxiliary contacts | V AC | 300 | ||
Mounting position | Vertical and 90° in all directions | |||
123I692
| With XFI earth-fault release: | |||
– NZM1, N1, NZM2, N2: vertical and 90° in all directions | ||||
with plug-in unit | ||||
– NZM1, N1, NZM2, N2: vertical, 90° right/left | ||||
with withdrawable unit: | ||||
– NZM3, N3: vertical, 90° right/left | ||||
– NZM4, N4: vertical | ||||
with remote operator: | ||||
– NZM2, N(S)2, NZM3, N(S)3, NZM4, N(S)4: vertical and 90° in all directions | ||||
Direction of incoming supply | as required | |||
Degree of protection | ||||
Device | In the operating controls area: IP20 (basic degree of protection) | |||
Enclosures | With insulating surround: IP40 With door coupling rotary handle: IP66 | |||
Terminations | Tunnel terminal: IP10 Phase isolator and strip terminal: IP00 | |||
Other technical data (sheet catalogue) | Temperature dependency, Derating | |||
Circuit-breakers | ||||
Rated current = rated uninterrupted current | In = Iu | A | 40 | |
Rated surge voltage invariability | Uimp | |||
Main contacts | V | 6000 | ||
Auxiliary contacts | V | 6000 | ||
Rated operational voltage | Ue | V AC | 690 | |
Rated operational voltage | Ue | V DC | 450 | |
0000SWI-6
| ||||
Overvoltage category/pollution degree | III/3 | |||
Rated insulation voltage | Ui | V | 690 | |
Use in unearthed supply systems | V | ≦ 690 | ||
Switching capacity | ||||
Rated short-circuit making capacity | Icm | |||
240 V | Icm | kA | 187 | |
400/415 V | Icm | kA | 105 | |
440 V 50/60 Hz | Icm | kA | 74 | |
525 V 50/60 Hz | Icm | kA | 40 | |
690 V 50/60 H | Ic | kA | 17 | |
Rated short-circuit breaking capacity Icn | Icn | |||
Icu to IEC/EN 60947 test cycle O-t-CO | Icu | kA | ||
240 V 50/60 Hz | Icu | kA | 85 | |
400/415 V 50/60 Hz | Icu | kA | 50 | |
440 V 50/60 Hz | Icu | kA | 35 | |
525 V 50/60 Hz | Icu | kA | 20 | |
690 V 50/60 Hz | Icu | kA | 10 | |
450 V DC | Icu | kA | 15 | |
Ics to IEC/EN 60947 test cycle O-t-CO-t-CO | Ics | kA | ||
240 V 50/60 Hz | Ics | kA | 85 | |
400/415 V 50/60 Hz | Ics | kA | 50 | |
440 V 50/60 Hz | Ics | kA | 35 | |
525 V 50/60 Hz | Ics | kA | 10 | |
690 V 50/60 Hz | Ics | kA | 7.5 | |
450 V DC | Ics | kA | 15 | |
Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker. | ||||
Utilization category to IEC/EN 60947-2 | A | |||
Lifespan, mechanical(of which max. 50 % trip by shunt/undervoltage release) | Operations | 20000 | ||
Lifespan, electrical | ||||
AC-1 | ||||
400 V 50/60 Hz | Operations | 10000 | ||
415 V 50/60 Hz | Operations | 10000 | ||
690 V 50/60 Hz | Operations | 7500 | ||
DC-1 | ||||
450 V DC | Operations | 10000 | ||
Max. operating frequency | Ops/h | 120 | ||
Total break time at short-circuit | ms | < 10 | ||
Terminal capacity | ||||
Standard equipment | Box terminal | |||
Optional accessories | Screw connection Tunnel terminal connection on rear | |||
Round copper conductor | ||||
Box terminal | ||||
Solid | mm2 | 1 x (10 – 16) 2 x (6 – 16) | ||
Stranded | mm2 | 1 x (10 – 70) 3) 2 x (6-25) | ||
3) Up to 95 mm² can be connected depending on the cable manufacturer. | ||||
Tunnel terminal | ||||
Solid | mm2 | 1 x 16 | ||
Stranded | ||||
1-hole | mm2 | 1 x (25 – 95) | ||
Bolt terminal and rear-side connection | ||||
Direct on the switch | ||||
Solid | mm2 | 1 x (10 – 16) 2 x (6 – 16) | ||
Stranded | mm2 | 1 x (10 – 70) 3) 2 x 25 | ||
3) Up to 95 mm² can be connected depending on the cable manufacturer. | ||||
Al circular conductor | ||||
Tunnel terminal | ||||
Solid | mm2 | 1 x 16 | ||
Stranded | ||||
Stranded | mm2 | 1 x (25 – 95) | ||
Bolt terminal and rear-side connection | ||||
Direct on the switch | ||||
Solid | mm2 | 1 x (10 – 16) 2 x (10 – 16) | ||
Stranded | mm2 | 1 x (25 – 35) 2 x (25 – 35) | ||
Cu strip (number of segments x width x segment thickness) | ||||
Box terminal | ||||
min. | mm | 2 x 9 x 0.8 | ||
max. | mm | 9 x 9 x 0.8 | ||
Copper busbar (width x thickness) | mm | |||
Bolt terminal and rear-side connection | ||||
Screw connection | M6 | |||
Direct on the switch | ||||
min. | mm | 12 x 5 | ||
max. | mm | 16 x 5 | ||
Control cables | ||||
mm2 | 1 x (0.75 – 2.5) 2 x (0.75 – 1.5) | |||
Design verification as per IEC/EN 61439 | ||||
Technical data for design verification | ||||
Rated operational current for specified heat dissipation | In | A | 40 | |
Equipment heat dissipation, current-dependent | Pvid | W | 10.66 | |
Operating ambient temperature min. | °C | -25 | ||
Operating ambient temperature max. | °C | 70 | ||
IEC/EN 61439 design verification | ||||
10.2 Strength of materials and parts | ||||
10.2.2 Corrosion resistance | Meets the product standard’s requirements. | |||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard’s requirements. | |||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard’s requirements. | |||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard’s requirements. | |||
10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard’s requirements. | |||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. | |||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. | |||
10.2.7 Inscriptions | Meets the product standard’s requirements. | |||
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. | |||
10.4 Clearances and creepage distances | Meets the product standard’s requirements. | |||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. | |||
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. | |||
10.7 Internal electrical circuits and connections | Is the panel builder’s responsibility. | |||
10.8 Connections for external conductors | Is the panel builder’s responsibility. | |||
10.9 Insulation properties | ||||
10.9.2 Power-frequency electric strength | Is the panel builder’s responsibility. | |||
10.9.3 Impulse withstand voltage | Is the panel builder’s responsibility. | |||
10.9.4 Testing of enclosures made of insulating material | Is the panel builder’s responsibility. | |||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | |||
10.11 Short-circuit rating | Is the panel builder’s responsibility. The specifications for the switchgear must be observed. | |||