EATON 50716 T0-2-8241/E 1x20A Pako Şalter (3 Kademeli,sıfırlı)

Datasheet – T0-2-8241/E
Part no.T0-2-8241/E
Article no.050716
Catalog No.050716
1150PIC-420
Similar to illustration
Delivery program
Product rangeControl switches
Part group referenceT0
Basic functionStep switches
with black thumb grip and front plate
Contacts3
Number of steps3 steps, 45°
Degree of ProtectionFront IP65
Designflush mounting
000Z079
Contact sequence115S300-2
Switching angle°45
Switching performancemaintained

With 0 (Off) position

Design number8241
Front plate no.115K017
front plate0-3
Motor rating AC-23A, 50 – 60 Hz
400 VPkW5.5
Rated uninterrupted currentIuA20
Note on rated uninterrupted current !uRated uninterrupted current Iu is specified for max. cross-section.
Number of contact unitscontact unit(s)2
Technical data
General
StandardsIEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL

Switch-disconnector according to IEC/EN 60947-3

Climatic proofingDamp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature
Open°C-25 – +50
Enclosed°C-25 – +40
Overvoltage category/pollution degreeIII/3
Rated impulse withstand voltageUimpV AC6000
Mechanical shock resistanceg15
Mounting positionAs required
Contacts
Electrical characteristics
Rated operational voltageUeV AC690
Rated uninterrupted currentIuA20
Note on rated uninterrupted current !uRated uninterrupted current Iu is specified for max. cross-section.
Load rating with intermittent operation, class 12
AB 25 % DFx Ie2
AB 40 % DFx Ie1.6
AB 60 % DFx Ie1.3
Short-circuit rating
FuseA gG/gL20
Rated short-time withstand current (1 s current)IcwArms320
Note on rated short-time withstand current lcwCurrent for a time of 1 second
Rated conditional short-circuit currentIqkA6
Switching capacity
cos ϕ rated making capacity as per IEC 60947-3A130
Rated breaking capacity cos ϕ to IEC 60947-3A
230 VA100
400/415 VA110
500 VA80
690 VA60
Safe isolation to EN 61140
between the contactsV AC440
Current heat loss per contact at IeW0.6
Current heat loss per auxiliary circuit at Ie (AC-15/230 V)CO0.6
Lifespan, mechanicalOperationsx 106> 0.4
Maximum operating frequencyOperations/h1200
AC
AC-3
Rating, motor load switchPkW
220 V 230 VPkW3
230 V Star-deltaPkW5.5
400 V 415 VPkW5.5
400 V Star-deltaPkW7.5
500 VPkW5.5
500 V Star-deltaPkW7.5
690 VPkW4
690 V Star-deltaPkW5.5
Rated operational current motor load switch
230 VIeA11.5
230 V star-deltaIeA20
400V 415 VIeA11.5
400 V star-deltaIeA20
500 VIeA9
500 V star-deltaIeA15.6
690 VIeA4.9
690 V star-deltaIeA8.5
AC-23A
Motor rating AC-23A, 50 – 60 HzPkW
230 VPkW3
400 V 415 VPkW5.5
500 VPkW7.5
690 VPkW5.5
Rated operational current motor load switch
230 VIeA13.3
400 V 415 VIeA13.3
500 VIeA13.3
690 VIeA7.6
DC
DC-1, Load-break switches L/R = 1 ms
Rated operational currentIeA10
Voltage per contact pair in seriesV60
DC-21AIeA
Rated operational currentIeA1
ContactsQuantity1
DC-23A, motor load switch

L/R = 15 ms

24 V
Rated operational currentIeA10
ContactsQuantity1
48 V
Rated operational currentIeA10
ContactsQuantity2
60 V
Rated operational currentIeA10
ContactsQuantity3
120 V
Rated operational currentIeA5
ContactsQuantity3
240 V
Rated operational currentIeA5
ContactsQuantity5
DC-13, Control switches L/R = 50 ms
Rated operational currentIeA10
Voltage per contact pair in seriesV32
Control circuit reliability at 24 V DC, 10 mAFault probabilityHF-5,< 1 failure in 100,000 switching operations
Terminal capacities
Solid or strandedmm21 x (1 – 2,5)

2 x (1 – 2,5)

Flexible with ferrules to DIN 46228mm21 x (0.75 – 2.5)

2 x (0.75 – 2.5)

Terminal screwM3.5
Tightening torque for terminal screwNm1
Technical safety parameters:
NotesB10d values as per EN ISO 13849-1, table C1
Rating data for approved types
Contacts
Rated operational voltageUeV AC600
Rated uninterrupted current max.
Main conducting paths
General useA16
Auxiliary contacts
General UseIUA10
Pilot DutyA 600

P 300

Switching capacity
Maximum motor rating
Single-phase
120 V ACHP0.5
200 V ACHP1
240 V ACHP1.5
Three-phase
200 V ACHP3
240 V ACHP3
480 V ACHP7.5
600 V ACHP7.5
Short Circuit Current RatingSCCR
Basic RatingkA5
max. FuseA50
High fault ratingkA10
max. FuseA20, Class J
Terminal capacity
Solid or flexible conductor with ferruleAWG18 – 14
Terminal screwM3.5
Tightening torquelb-in8.8
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipationInA20
Heat dissipation per pole, current-dependentPvidW0.6
Equipment heat dissipation, current-dependentPvidW0
Static heat dissipation, non-current-dependentPvsW0
Heat dissipation capacityPdissW0
Operating ambient temperature min.°C-25
Operating ambient temperature max.°C50
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistanceMeets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard’s requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effectsMeets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiationUV resistance only in connection with protective shield.
10.2.5 LiftingDoes not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.
10.2.7 InscriptionsMeets the product standard’s requirements.
10.3 Degree of protection of ASSEMBLIESDoes not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distancesMeets the product standard’s requirements.
10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connectionsIs the panel builder’s responsibility.
10.8 Connections for external conductorsIs the panel builder’s responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strengthIs the panel builder’s responsibility.
10.9.3 Impulse withstand voltageIs the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating materialIs the panel builder’s responsibility.
10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit ratingIs the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibilityIs the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Control switch (EC002611)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Control switch (ecl@ss10.0.1-27-37-14-14 [ACN998011])
Type of switchLevel switch
Number of poles1
Max. rated operation voltage Ue ACV690
Rated permanent current IuA20
Number of switch positions4
With 0 (off) positionYes
With retraction in 0-positionNo
Device constructionBuilt-in device
Width in number of modular spacings0
Suitable for ground mountingNo
Suitable for front mounting 4-holeYes
Suitable for distribution board installationNo
Suitable for intermediate mountingNo
Complete device in housingNo
Type of control elementToggle
Front shield size48×48 mm
Degree of protection (IP), front sideIP65
Degree of protection (NEMA), front side12