EATON 286533 1x16A 6kA C Tipi Otomatik Sigorta

Marka: Eaton
0,00
10.000₺ ve üzeri alışverişlerinize özel teklif.
Datasheet – PL6-C16/1
Part no.PL6-C16/1
Article no.286533
Catalog No.286533
wa_sg88420_l
wa_sg88420_c
wa_sg88420_r
Similar to illustration
Delivery program
Basic functionMiniature circuit-breakers
Number of poles1 pole
Tripping characteristicC
ApplicationSwitchgear for residential and commercial applications
Rated currentInA16
Rated switching capacity according to IEC/EN 60898-1IcnkA6
Product rangePL6
Technical data
Electrical
Rated switching capacity according to IEC/EN 60898-1IcnkA6
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipationInA16
Heat dissipation per pole, current-dependentPvidW0
Equipment heat dissipation, current-dependentPvidW2.2
Static heat dissipation, non-current-dependentPvsW0
Heat dissipation capacityPdissW0
Operating ambient temperature min.°C-25
Operating ambient temperature max.°C75
linear, per +1 °C, results in a 0.5% reduction of current carrying capacity
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistanceMeets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard’s requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effectsMeets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiationMeets the product standard’s requirements.
10.2.5 LiftingDoes not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.
10.2.7 InscriptionsMeets the product standard’s requirements.
10.3 Degree of protection of ASSEMBLIESDoes not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distancesMeets the product standard’s requirements.
10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connectionsIs the panel builder’s responsibility.
10.8 Connections for external conductorsIs the panel builder’s responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strengthIs the panel builder’s responsibility.
10.9.3 Impulse withstand voltageIs the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating materialIs the panel builder’s responsibility.
10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit ratingIs the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibilityIs the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 7.0
Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042)
Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) (ecl@ss10.0.1-27-14-19-01 [AAB905014])
Release characteristicC
Number of poles (total)1
Number of protected poles1
Rated currentA16
Rated voltageV230
Rated insulation voltage UiV440
Rated impulse withstand voltage UimpkV4
Rated short-circuit breaking capacity Icn EN 60898 at 230 VkA6
Rated short-circuit breaking capacity Icn EN 60898 at 400 VkA6
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 VkA0
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 VkA0
Voltage typeAC
FrequencyHz50 – 60
Current limiting class3
Suitable for flush-mounted installationNo
Concurrently switching N-neutralNo
Over voltage category3
Pollution degree2
Additional equipment possibleYes
Width in number of modular spacings1
Built-in depthmm70.5
Degree of protection (IP)IP20
Ambient temperature during operating°C-25 – 75
Connectable conductor cross section multi-wiredmm²1 – 25
Connectable conductor cross section solid-coremm²1 – 25