EATON 248038 3x63A 25kA C Tipi Otomatik Sigorta
Marka: Eaton
0,00₺
10.000₺ ve üzeri alışverişlerinize özel teklif.
Datasheet – PLHT-C63/3 | |||
Part no. | PLHT-C63/3 | ||
Article no. | 248038 | ||
Catalog No. | 248038 | ||
sg43111 | |||
Similar to illustration | |||
Delivery program | |||
Basic function | Miniature circuit-breakers | ||
Number of poles | 3 pole | ||
Tripping characteristic | C | ||
Application | Switchgear for industrial and advanced commercial applications | ||
Rated current | In | A | 63 |
Rated switching capacity acc. to IEC/EN 60947-2 | Icu | kA | 25 |
Product range | PLHT | ||
Technical data | |||
Electrical | |||
Rated switching capacity acc. to IEC/EN 60947-2 | Icu | kA | 25 |
Design verification as per IEC/EN 61439 | |||
Technical data for design verification | |||
Rated operational current for specified heat dissipation | In | A | 63 |
Heat dissipation per pole, current-dependent | Pvid | W | 0 |
Equipment heat dissipation, current-dependent | Pvid | W | 15.6 |
Static heat dissipation, non-current-dependent | Pvs | W | 0 |
Heat dissipation capacity | Pdiss | W | 0 |
Operating ambient temperature min. | °C | -25 | |
Operating ambient temperature max. | °C | 55 | |
linear, per +1 °C, results in a 0.35% reduction of current carrying capacity | |||
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard’s requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard’s requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard’s requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard’s requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard’s requirements. | ||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.7 Inscriptions | Meets the product standard’s requirements. | ||
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.4 Clearances and creepage distances | Meets the product standard’s requirements. | ||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.7 Internal electrical circuits and connections | Is the panel builder’s responsibility. | ||
10.8 Connections for external conductors | Is the panel builder’s responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Is the panel builder’s responsibility. | ||
10.9.3 Impulse withstand voltage | Is the panel builder’s responsibility. | ||
10.9.4 Testing of enclosures made of insulating material | Is the panel builder’s responsibility. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder’s responsibility. The specifications for the switchgear must be observed. | ||
10.12 Electromagnetic compatibility | Is the panel builder’s responsibility. The specifications for the switchgear must be observed. | ||
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | ||
Technical data ETIM 7.0 | |||
Circuit breakers and fuses (EG000020) / Miniature circuit breaker (MCB) (EC000042) | |||
Electric engineering, automation, process control engineering / Electrical installation, device / Miniature circuit breaker system (MCB) / Miniature circuit breaker (MCB) (ecl@ss10.0.1-27-14-19-01 [AAB905014]) | |||
Release characteristic | C | ||
Number of poles (total) | 3 | ||
Number of protected poles | 3 | ||
Rated current | A | 63 | |
Rated voltage | V | 400 | |
Rated insulation voltage Ui | V | 440 | |
Rated impulse withstand voltage Uimp | kV | 4 | |
Rated short-circuit breaking capacity Icn EN 60898 at 230 V | kA | 0 | |
Rated short-circuit breaking capacity Icn EN 60898 at 400 V | kA | 0 | |
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V | kA | 25 | |
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V | kA | 25 | |
Voltage type | AC | ||
Frequency | Hz | 50 – 60 | |
Current limiting class | 3 | ||
Suitable for flush-mounted installation | No | ||
Concurrently switching N-neutral | No | ||
Over voltage category | 3 | ||
Pollution degree | 2 | ||
Additional equipment possible | Yes | ||
Width in number of modular spacings | 4.5 | ||
Built-in depth | mm | 75 | |
Degree of protection (IP) | IP20 | ||
Ambient temperature during operating | °C | -25 – 55 | |
Connectable conductor cross section multi-wired | mm² | 2.5 – 50 | |
Connectable conductor cross section solid-core | mm² | 2.5 – 50 |