Datasheet – PKZM4-40-EA
Part no.PKZM4-40-EA
Article no.190021
Catalog No.190021
1210PIC-459
Delivery program
Product rangePKZM4 motor protective circuit-breakers up to 65 A
Basic functionMotor protection
0000SPC-571
NotesAlso suitable for motors with efficiency class IE3.
Connection techniqueScrew terminals
Contact sequence121S003
Max. motor rating
AC-3
220 V 230 V 240 VPkW11
380 V 400 V 415 VPkW20
440 VPkW22
500 VPkW24
660 V 690 VPkW30
Rated uninterrupted currentIuA40
Setting range
Overload releasesIrA32 – 40
short-circuit release
max.IrmA620
Phase-failure sensitivityIEC/EN 60947-4-1, VDE 0660 Part 102
NotesOverload trigger: tripping class 10 A

Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height.

Technical data
General
StandardsIEC/EN 60947, VDE 0660,UL, CSA
Climatic proofingDamp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature
Storage°C– 40 – 80
Open°C-25 – +55
Enclosed°C– 25 – 40
Mounting position1210DRW-68
Direction of incoming supplyas required
Degree of protection
DeviceIP20
TerminationsIP00
Protection against direct contact when actuated from front (EN 50274)Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27g15
AltitudemMax. 2000
Terminal capacity main cable
Screw terminals
Solidmm21 x (0.75 – 16)

2 x (0.75 – 16)

Flexible with ferrule to DIN 46228mm21 x (0.75 – 35)

2 x (0.75 – 25)

Solid or strandedAWG14 – 1
Stripping lengthmm14
Specified tightening torque for terminal screws
Main cableNm3.3
Main conducting paths
Rated impulse withstand voltageUimpV AC6000
Overvoltage category/pollution degreeIII/3
Rated operational voltageUeV AC690
Rated uninterrupted current = rated operational currentIu = IeA40
Rated frequencyfHz40 – 60
Current heat loss (3 pole at operating temperature)W20.7
Impedance per polemΩ5
Lifespan, mechanicalOperationsx 1060.03
Lifespan, electrical (AC-3 at 400 V)
Lifespan, electricalOperationsx 1060.03
Max. operating frequencyOps/h40
Short-circuit rating
DC
Short-circuit ratingkA60
Notesup to 250 V
Motor switching capacity
AC-3 (up to 690V)A40
DC-5 (up to 250V)A40 (3 contacts in series)
Trip blocks
Temperature compensation
to IEC/EN 60947, VDE 0660°C– 5…40
Operating range°C– 25…55
Temperature compensation residual error for T > 40 °C≦ 0.25 %/K
Setting range of overload releasesx Iu0.6 – 1
short-circuit releaseBasic device, fixed: 15.5 x Iu
Short-circuit release tolerance± 20%
Phase-failure sensitivityIEC/EN 60947-4-1, VDE 0660 Part 102
Rating data for approved types
Switching capacity
Maximum motor rating
Three-phase
200 V

208 V

HP10
460 V

480 V

HP30
575 V

600 V

HP30
Single-phase
115 V

120 V

HP3
230 V

240 V

HP7.5
Short Circuit Current Rating, type ESCCR
240 VkA65
480 Y / 277 VkA65
600 Y / 347 VkA25
Accessories requiredBK50/3-PKZ4-E
Short Circuit Current Rating, group protectionSCCR
600 V High Fault
SCCR (fuse)kA42
max. FuseA600
SCCR (CB)kA42
max. CBA600
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipationInA40
Heat dissipation per pole, current-dependentPvidW6.9
Equipment heat dissipation, current-dependentPvidW20.7
Static heat dissipation, non-current-dependentPvsW0
Heat dissipation capacityPdissW0
Operating ambient temperature min.°C-25
Operating ambient temperature max.°C55
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistanceMeets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard’s requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effectsMeets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiationMeets the product standard’s requirements.
10.2.5 LiftingDoes not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.
10.2.7 InscriptionsMeets the product standard’s requirements.
10.3 Degree of protection of ASSEMBLIESDoes not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distancesMeets the product standard’s requirements.
10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connectionsIs the panel builder’s responsibility.
10.8 Connections for external conductorsIs the panel builder’s responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strengthIs the panel builder’s responsibility.
10.9.3 Impulse withstand voltageIs the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating materialIs the panel builder’s responsibility.
10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit ratingIs the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibilityIs the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Motor protection circuit-breaker (ecl@ss10.0.1-27-37-04-01 [AGZ529016])
Overload release current settingA32 – 40
Adjustment range undelayed short-circuit releaseA620 – 620
With thermal protectionYes
Phase failure sensitiveYes
Switch off techniqueThermomagnetic
Rated operating voltageV690 – 690
Rated permanent current IuA40
Rated operation power at AC-3, 230 VkW11
Rated operation power at AC-3, 400 VkW20
Type of electrical connection of main circuitScrew connection
Type of control elementTurn button
Device constructionBuilt-in device fixed built-in technique
With integrated auxiliary switchNo
With integrated under voltage releaseNo
Number of poles3
Rated short-circuit breaking capacity lcu at 400 V, ACkA50
Degree of protection (IP)IP20
Heightmm140
Widthmm55
Depthmm160
Approvals
Product StandardsIEC/EN 60947-4-1; UL 60947-4-1; CSA – C22.2 No. 60947-4-1-14; CE marking
UL File No.E36332
UL Category Control No.NLRV
CSA File No.165628
CSA Class No.3211-05
North America CertificationUL listed, CSA certified
Specially designed for North AmericaNo
Suitable forBranch circuit: Manual type E if used with terminal, or suitable for group installations
Characteristics
1210CON-21
1: Standard auxiliary contact

2: Trip-indicating auxiliary contact

3: Shunt releases, undervoltage releases

121U043
Tripping characteristics motor-protective circuit breaker PKZM4-…

1: Minimum level, 3-phase

2: Maximum level, 3-phase

3: Minimum marker, 2-phase

4: Highest marker, 2-phase

121U029
Let-through current
121U028
① 1 half-cycle

Let-through energy

Dimensions
1210DIM-29
121X073
PKZM4-… +AK-PKZ0
Additional product information (links)
Schaltvermögen
Motor starters and “Special Purpose Ratings” for the North American market
Busbar Component Adapters for modern Industrial control panels