EATON 190021 32-40AMotor Koruma Şalteri
Marka: Eaton
Orijinal fiyat: 7.071,60₺.2.475,06₺Şu andaki fiyat: 2.475,06₺.
10.000₺ ve üzeri alışverişlerinize özel teklif.
Datasheet – PKZM4-40-EA | |||
Part no. | PKZM4-40-EA | ||
Article no. | 190021 | ||
Catalog No. | 190021 | ||
1210PIC-459 | |||
Delivery program | |||
Product range | PKZM4 motor protective circuit-breakers up to 65 A | ||
Basic function | Motor protection | ||
0000SPC-571 | |||
Notes | Also suitable for motors with efficiency class IE3. | ||
Connection technique | Screw terminals | ||
Contact sequence | 121S003 | ||
Max. motor rating | |||
AC-3 | |||
220 V 230 V 240 V | P | kW | 11 |
380 V 400 V 415 V | P | kW | 20 |
440 V | P | kW | 22 |
500 V | P | kW | 24 |
660 V 690 V | P | kW | 30 |
Rated uninterrupted current | Iu | A | 40 |
Setting range | |||
Overload releases | Ir | A | 32 – 40 |
short-circuit release | |||
max. | Irm | A | 620 |
Phase-failure sensitivity | IEC/EN 60947-4-1, VDE 0660 Part 102 | ||
NotesOverload trigger: tripping class 10 A Can be snapped on to IEC/EN 60715 top-hat rail with 7.5 or 15 mm height. | |||
Technical data | |||
General | |||
Standards | IEC/EN 60947, VDE 0660,UL, CSA | ||
Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 | ||
Ambient temperature | |||
Storage | °C | – 40 – 80 | |
Open | °C | -25 – +55 | |
Enclosed | °C | – 25 – 40 | |
Mounting position | 1210DRW-68 | ||
Direction of incoming supply | as required | ||
Degree of protection | |||
Device | IP20 | ||
Terminations | IP00 | ||
Protection against direct contact when actuated from front (EN 50274) | Finger and back-of-hand proof | ||
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC 60068-2-27 | g | 15 | |
Altitude | m | Max. 2000 | |
Terminal capacity main cable | |||
Screw terminals | |||
Solid | mm2 | 1 x (0.75 – 16) 2 x (0.75 – 16) | |
Flexible with ferrule to DIN 46228 | mm2 | 1 x (0.75 – 35) 2 x (0.75 – 25) | |
Solid or stranded | AWG | 14 – 1 | |
Stripping length | mm | 14 | |
Specified tightening torque for terminal screws | |||
Main cable | Nm | 3.3 | |
Main conducting paths | |||
Rated impulse withstand voltage | Uimp | V AC | 6000 |
Overvoltage category/pollution degree | III/3 | ||
Rated operational voltage | Ue | V AC | 690 |
Rated uninterrupted current = rated operational current | Iu = Ie | A | 40 |
Rated frequency | f | Hz | 40 – 60 |
Current heat loss (3 pole at operating temperature) | W | 20.7 | |
Impedance per pole | mΩ | 5 | |
Lifespan, mechanical | Operations | x 106 | 0.03 |
Lifespan, electrical (AC-3 at 400 V) | |||
Lifespan, electrical | Operations | x 106 | 0.03 |
Max. operating frequency | Ops/h | 40 | |
Short-circuit rating | |||
DC | |||
Short-circuit rating | kA | 60 | |
Notes | up to 250 V | ||
Motor switching capacity | |||
AC-3 (up to 690V) | A | 40 | |
DC-5 (up to 250V) | A | 40 (3 contacts in series) | |
Trip blocks | |||
Temperature compensation | |||
to IEC/EN 60947, VDE 0660 | °C | – 5…40 | |
Operating range | °C | – 25…55 | |
Temperature compensation residual error for T > 40 °C | ≦ 0.25 %/K | ||
Setting range of overload releases | x Iu | 0.6 – 1 | |
short-circuit release | Basic device, fixed: 15.5 x Iu | ||
Short-circuit release tolerance | ± 20% | ||
Phase-failure sensitivity | IEC/EN 60947-4-1, VDE 0660 Part 102 | ||
Rating data for approved types | |||
Switching capacity | |||
Maximum motor rating | |||
Three-phase | |||
200 V 208 V | HP | 10 | |
460 V 480 V | HP | 30 | |
575 V 600 V | HP | 30 | |
Single-phase | |||
115 V 120 V | HP | 3 | |
230 V 240 V | HP | 7.5 | |
Short Circuit Current Rating, type E | SCCR | ||
240 V | kA | 65 | |
480 Y / 277 V | kA | 65 | |
600 Y / 347 V | kA | 25 | |
Accessories required | BK50/3-PKZ4-E | ||
Short Circuit Current Rating, group protection | SCCR | ||
600 V High Fault | |||
SCCR (fuse) | kA | 42 | |
max. Fuse | A | 600 | |
SCCR (CB) | kA | 42 | |
max. CB | A | 600 | |
Design verification as per IEC/EN 61439 | |||
Technical data for design verification | |||
Rated operational current for specified heat dissipation | In | A | 40 |
Heat dissipation per pole, current-dependent | Pvid | W | 6.9 |
Equipment heat dissipation, current-dependent | Pvid | W | 20.7 |
Static heat dissipation, non-current-dependent | Pvs | W | 0 |
Heat dissipation capacity | Pdiss | W | 0 |
Operating ambient temperature min. | °C | -25 | |
Operating ambient temperature max. | °C | 55 | |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard’s requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard’s requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard’s requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard’s requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard’s requirements. | ||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.7 Inscriptions | Meets the product standard’s requirements. | ||
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.4 Clearances and creepage distances | Meets the product standard’s requirements. | ||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.7 Internal electrical circuits and connections | Is the panel builder’s responsibility. | ||
10.8 Connections for external conductors | Is the panel builder’s responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Is the panel builder’s responsibility. | ||
10.9.3 Impulse withstand voltage | Is the panel builder’s responsibility. | ||
10.9.4 Testing of enclosures made of insulating material | Is the panel builder’s responsibility. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder’s responsibility. The specifications for the switchgear must be observed. | ||
10.12 Electromagnetic compatibility | Is the panel builder’s responsibility. The specifications for the switchgear must be observed. | ||
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | ||
Technical data ETIM 7.0 | |||
Low-voltage industrial components (EG000017) / Motor protection circuit-breaker (EC000074) | |||
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Motor protection circuit-breaker (ecl@ss10.0.1-27-37-04-01 [AGZ529016]) | |||
Overload release current setting | A | 32 – 40 | |
Adjustment range undelayed short-circuit release | A | 620 – 620 | |
With thermal protection | Yes | ||
Phase failure sensitive | Yes | ||
Switch off technique | Thermomagnetic | ||
Rated operating voltage | V | 690 – 690 | |
Rated permanent current Iu | A | 40 | |
Rated operation power at AC-3, 230 V | kW | 11 | |
Rated operation power at AC-3, 400 V | kW | 20 | |
Type of electrical connection of main circuit | Screw connection | ||
Type of control element | Turn button | ||
Device construction | Built-in device fixed built-in technique | ||
With integrated auxiliary switch | No | ||
With integrated under voltage release | No | ||
Number of poles | 3 | ||
Rated short-circuit breaking capacity lcu at 400 V, AC | kA | 50 | |
Degree of protection (IP) | IP20 | ||
Height | mm | 140 | |
Width | mm | 55 | |
Depth | mm | 160 | |
Approvals | |||
Product Standards | IEC/EN 60947-4-1; UL 60947-4-1; CSA – C22.2 No. 60947-4-1-14; CE marking | ||
UL File No. | E36332 | ||
UL Category Control No. | NLRV | ||
CSA File No. | 165628 | ||
CSA Class No. | 3211-05 | ||
North America Certification | UL listed, CSA certified | ||
Specially designed for North America | No | ||
Suitable for | Branch circuit: Manual type E if used with terminal, or suitable for group installations | ||
Characteristics | |||
1210CON-21 | |||
1: Standard auxiliary contact 2: Trip-indicating auxiliary contact 3: Shunt releases, undervoltage releases | |||
121U043 | |||
Tripping characteristics motor-protective circuit breaker PKZM4-… 1: Minimum level, 3-phase 2: Maximum level, 3-phase 3: Minimum marker, 2-phase 4: Highest marker, 2-phase | |||
121U029 | |||
Let-through current | |||
121U028 | |||
① 1 half-cycle Let-through energy | |||
Dimensions | |||
1210DIM-29 | |||
121X073 | |||
PKZM4-… +AK-PKZ0 | |||
Additional product information (links) | |||
Schaltvermögen | |||
Motor starters and “Special Purpose Ratings” for the North American market | |||
Busbar Component Adapters for modern Industrial control panels |