EATON 189921 37kW Kontaktör

Marka: Eaton
0,00
10.000₺ ve üzeri alışverişlerinize özel teklif.

EATON 189921 DILM80-EA (230V50HZ,240V60HZ) 80A Güç Kontaktörü (AC bobin)

Datasheet – DILM80-EA(230V50HZ,240V60HZ)
Part no.DILM80-EA(230V50HZ,240V60HZ)
Article no.189921
Catalog No.189921
2110PIC-296
Delivery program
Product rangeContactors
ApplicationContactors for Motors
SubrangeContactors up to 170 A, 3 pole
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces

AC-3/AC-3e: Normal AC induction motors: Starting, switching off while running

AC-4: Normal AC induction motors: starting, plugging, reversing, inching

0000SPC-571
NotesAlso suitable for motors with efficiency class IE3.
Connection techniqueScrew terminals
Number of poles3 pole
Rated operational current
AC-3
NotesAt maximum permissible ambient temperature (open.)

Also tested according to AC-3e.

380 V 400 VIeA80
AC-1
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 40 °CIth =IeA110
enclosedIthA80
Conventional free air thermal current, 1 pole
openIthA225
enclosedIthA200
Max. rating for three-phase motors, 50 – 60 Hz
AC-3
220 V 230 VPkW25
380 V 400 VPkW37
660 V 690 VPkW63
AC-4
220 V 230 VPkW11.5
380 V 400 VPkW20
660 V 690 VPkW26
Contact sequence210S045
InstructionsContacts to EN 50 012.
Can be combined with auxiliary contactDILM150-XHI(V)…

DILM1000-XHI(V)…

Actuating voltage230 V 50 Hz, 240 V 60 Hz
Voltage AC/DCAC operation
Connection to SmartWire-DTno
Frame size4
Technical data
General
StandardsIEC/EN 60947, VDE 0660, UL, CSA
Lifespan, mechanical
AC operatedOperationsx 1065.7
Operating frequency, mechanical
AC operatedOperations/h3600
Climatic proofingDamp heat, constant, to IEC 60068-2-78

Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature
Open°C-25 – +60
Enclosed°C– 25 – 40
Storage°C– 40 – 80
Mounting position210N017
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock, 10 ms
Main contacts
N/O contactg10
Auxiliary contacts
N/O contactg7
N/C contactg5
Mechanical shock resistance (IEC/EN 60068-2-27) when tabletop-mounted
Half-sinusoidal shock, 10 ms
Main contacts
N/O contactg10
Auxiliary contacts
N/O contactg7
N/C contactg5
Degree of ProtectionIP00
Protection against direct contact when actuated from front (EN 50274)Finger and back-of-hand proof
Altitudemmax. 2000 m
Weight
AC operatedkg2.18
Screw connector terminals
Terminal capacity main cable
Flexible with ferrulemm21 x (10 – 95)

2 x (10 – 70)

Strandedmm21 x (16 – 95)

2 x (16 – 70)

Solid or strandedAWGsingle 8…3/0, double 8…2/0
Flat conductorLamellenzahl x Breite x Dickemm2 x (6 x 16 x 0.8)
Stripping lengthmm24
Terminal screwM10
Tightening torqueNm14
Tool
Hexagon socket-head spannerSWmm5
Terminal capacity control circuit cables
Solidmm21 x (0.75 – 4)

2 x (0.75 – 2.5)

Flexible with ferrulemm21 x (0.75 – 2.5)

2 x (0.75 – 2.5)

Solid or strandedAWG18 – 14
Stripping lengthmm10
Terminal screwM3.5
Tightening torqueNm1.2
Tool
Pozidriv screwdriverSize2
Standard screwdrivermm0.8 x 5.5

1 x 6

Main conducting paths
Rated impulse withstand voltageUimpV AC8000
Overvoltage category/pollution degreeIII/3
Rated insulation voltageUiV AC690
Rated operational voltageUeV AC690
Safe isolation to EN 61140
between coil and contactsV AC690
between the contactsV AC690
Making capacity (p.f. to IEC/EN 60947)
Up to 690 VA1120
Breaking capacity
220 V 230 VA800
380 V 400 VA800
500 VA800
660 V 690 VA650
Short-circuit rating
Short-circuit protection maximum fuse
Type “2” coordination
400 VgG/gL 500 VA160
690 VgG/gL 690 VA160
Type “1” coordination
400 VgG/gL 500 VA250
690 VgG/gL 690 VA200
AC
AC-1
Rated operational current
Conventional free air thermal current, 3 pole, 50 – 60 Hz
Open
at 40 °CIth =IeA110
at 50 °CIth =IeA98
at 55 °CIth =IeA94
at 60 °CIth =IeA90
enclosedIthA80
Conventional free air thermal current, 1 pole
openIthA225
enclosedIthA200
AC-3
Rated operational current
Open, 3-pole: 50 – 60 Hz
NotesAt maximum permissible ambient temperature (open.)

Also tested according to AC-3e.

220 V 230 VIeA80
240 VIeA80
380 V 400 VIeA80
415 VIeA80
440VIeA80
500 VIeA80
660 V 690 VIeA65
Motor ratingPkWh
220 V 230 VPkW25
240VPkW27.5
380 V 400 VPkW37
415 VPkW48
440 VPkW51
500 VPkW58
660 V 690 VPkW63
AC-4
Open, 3-pole: 50 – 60 Hz
220 V 230 VIeA40
240 VIeA40
380 V 400 VIeA40
415 VIeA40
440 VIeA40
500 VIeA40
660 V 690 VIeA27
Motor ratingPkWh
220 V 230 VPkW11.5
240 VPkW13
380 V 400 VPkW20
415 VPkW24
440 VPkW25
500 VPkW29
660 V 690 VPkW26
DC
Rated operational current, open
DC-1
60 VIeA110
110 VIeA110
220 VIeA70
Current heat loss
3 pole, at Ith (60°)W11.4
Current heat loss at Ie to AC-3/400 VW9
Impedance per polemΩ0.6
Magnet systems
Voltage tolerance
AC operatedPick-upx Uc0.8 – 1.1
Drop-out voltage AC operatedDrop-outx Uc0.3 – 0.6
Power consumption of the coil in a cold state and 1.0 x US
50 HzPick-upVA310
50 HzSealingVA26
50 HzSealingW5.8
60 HzPick-upVA345
60 HzSealingVA30
60 HzSealingW5.8
Duty factor% DF100
Changeover time at 100 % US (recommended value)
Main contacts
AC operated
Closing delayms14 – 20
Opening delayms9 – 14
Arcing time