EATON 259591 Açtırma Bobini

Marka: Eaton
0,00
10.000₺ ve üzeri alışverişlerinize özel teklif.

EATON 259591 NZM2/3 – NZM2/3-XUHIV208-240AC Kompakt Şalter Aksesuarı: Erken Kapama Kontaklı Düşük Gerilim Bobini

Datasheet – NZM2/3-XUHIV208-240AC
Part no.NZM2/3-XUHIV208-240AC
Article no.259591
Catalog No.259591
1230PIC-1134
Delivery program
Product rangeAccessories
AccessoriesUndervoltage release
AccessoriesUndervoltage release with early-make auxiliary contact
Standard/ApprovalUL/CSA, IEC
Construction sizeNZM2/3
DescriptionUndervoltage release with 2 early-make auxiliary contacts, e.g., for early-make connection of undervoltage release in main switch applications, as well as for interlock and load shedding circuits.

For use with emergency-stop devices in connection with an emergency-stop button.

When the under-voltage trip is switched off, accidental contact with the circuit breaker’s primary contacts is prevented when switched on.

Early make of auxiliary contacts on switching on and off (manual operation): approx. 20 ms

Undervoltage releases cannot be installed simultaneously with NZM…-XHIV… early-make auxiliary contact or NZM…-XA… shunt release.

Cannot be used in conjunction with NZM…-XR… remote operator.

Connection typeWith bolt connection
Auxiliary contactswith 2 early-make auxiliary contacts
Rated control voltageUsV208 – 240 V 50/60 Hz
For use withNZM2(-4), N(S)2(-4)

NZM3(-4), N(S)3(-4)

Technical data
Undervoltage release
Rated control voltageUsV
ACUsV AC208-240
Rated control voltageUsV208 – 240 V 50/60 Hz
Operating range
Drop-out voltagex Us0.35 – 0.7
Pick-up voltagex Uc0.85 – 1.1
Power consumption
AC
Pick-up ACVA1.5
Sealing ACVA1.5
DCx Us
Pick-up DCW0.8
Sealing DCW0.8
Maximum opening delay (response time until opening of the main contacts)ms19
Minimum command timems10 – 15
Terminal capacities
Solid or flexible conductor, with ferrulemm21 x (0,75 – 2,5)

2 x (0,75 – 2,5)

AWG1 x (18 … 14)

2 x (18 … 14)

Design verification as per IEC/EN 61439
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistanceMeets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard’s requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effectsMeets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiationMeets the product standard’s requirements.
10.2.5 LiftingDoes not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.
10.2.7 InscriptionsMeets the product standard’s requirements.
10.3 Degree of protection of ASSEMBLIESDoes not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distancesMeets the product standard’s requirements.
10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connectionsIs the panel builder’s responsibility.
10.8 Connections for external conductorsIs the panel builder’s responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strengthIs the panel builder’s responsibility.
10.9.3 Impulse withstand voltageIs the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating materialIs the panel builder’s responsibility.
10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit ratingIs the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibilityIs the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Under voltage coil (EC001022)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Undervoltage trip (ecl@ss10.0.1-27-37-04-17 [AKF015013])
Rated control supply voltage Us at AC 50HZV208 – 240
Rated control supply voltage Us at AC 60HZV208 – 240
Rated control supply voltage Us at DCV0 – 0
Voltage type for actuatingAC
Type of electric connectionScrew connection
Number of contacts as normally open contact2
Number of contacts as normally closed contact0
Number of contacts as change-over contact0
DelayedNo
Suitable for power circuit breakerYes
Suitable for off-load switchYes
Suitable for motor safety switchNo
Suitable for overload relayNo
Approvals
Product StandardsUL489; CSA-C22.2 No. 5-09; IEC60947, CE marking
UL File No.E140305
UL Category Control No.DIHS
CSA File No.022086
CSA Class No.1437-01
North America CertificationUL listed, CSA certified