Datasheet – BZMB1-A40 | |||
Part no. | BZMB1-A40 | ||
Article no. | 109720 | ||
Catalog No. | 109720 | ||
sg02310 | |||
Similar to illustration | |||
Design verification as per IEC/EN 61439 | |||
Technical data for design verification | |||
Rated operational current for specified heat dissipation | In | A | 40 |
Equipment heat dissipation, current-dependent | Pvid | W | 10.6 |
IEC/EN 61439 design verification | |||
10.2 Strength of materials and parts | |||
10.2.2 Corrosion resistance | Meets the product standard’s requirements. | ||
10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard’s requirements. | ||
10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard’s requirements. | ||
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | Meets the product standard’s requirements. | ||
10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard’s requirements. | ||
10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.7 Inscriptions | Meets the product standard’s requirements. | ||
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.4 Clearances and creepage distances | Meets the product standard’s requirements. | ||
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. | ||
10.7 Internal electrical circuits and connections | Is the panel builder’s responsibility. | ||
10.8 Connections for external conductors | Is the panel builder’s responsibility. | ||
10.9 Insulation properties | |||
10.9.2 Power-frequency electric strength | Is the panel builder’s responsibility. | ||
10.9.3 Impulse withstand voltage | Is the panel builder’s responsibility. | ||
10.9.4 Testing of enclosures made of insulating material | Is the panel builder’s responsibility. | ||
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | ||
10.11 Short-circuit rating | Is the panel builder’s responsibility. The specifications for the switchgear must be observed. | ||
10.12 Electromagnetic compatibility | Is the panel builder’s responsibility. The specifications for the switchgear must be observed. | ||
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | ||
Technical data ETIM 7.0 | |||
Low-voltage industrial components (EG000017) / Power circuit-breaker for trafo/generator/installation protection (EC000228) | |||
Electric engineering, automation, process control engineering / Low-voltage switch technology / Circuit breaker (LV < 1 kV) / Circuit breaker for power transformer, generator and system protection (ecl@ss10.0.1-27-37-04-09 [AJZ716013]) | |||
Rated permanent current Iu | A | 40 | |
Rated voltage | V | 415 – 415 | |
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz | kA | 25 | |
Overload release current setting | A | 0 – 0 | |
Adjustment range short-term delayed short-circuit release | A | 0 – 0 | |
Adjustment range undelayed short-circuit release | A | 320 – 480 | |
Integrated earth fault protection | No | ||
Type of electrical connection of main circuit | Screw connection | ||
Device construction | Built-in device fixed built-in technique | ||
Suitable for DIN rail (top hat rail) mounting | No | ||
DIN rail (top hat rail) mounting optional | Yes | ||
Number of auxiliary contacts as normally closed contact | 0 | ||
Number of auxiliary contacts as normally open contact | 0 | ||
Number of auxiliary contacts as change-over contact | 0 | ||
With switched-off indicator | No | ||
With under voltage release | No | ||
Number of poles | 3 | ||
Position of connection for main current circuit | Front side | ||
Type of control element | Rocker lever | ||
Complete device with protection unit | Yes | ||
Motor drive integrated | No | ||
Motor drive optional | No | ||
Degree of protection (IP) | IP20 |
EATON NE İŞ YAPAR ?
Bugün dünyamız kritik altyapı ve teknoloji üzerinde dönüyor. Uçaklar… Hastaneler… Fabrikalar… Veri merkezleri… Araçlar… Elektrik şebekesi… Günümüzde insanların her gün ihtiyaç duyduğu şeyler vardır. Ve şirketler de gezegenimizdeki en büyük güç zorluklarından bazılarının üstesinden gelmelerine yardımcı olmamız için bize güvenmektedir. Eaton’da, daha güvenilir, daha verimli ve daha emniyetli güç yönetimi teknolojileriyle insanların hayatını ve çevreyi iyileştirmeye kendimizi adamış bulunuyoruz.
Biz, 99,000’den fazla çalışana sahip ve 175’ten fazla ülkede iş yapan bir güç yönetim şirketiyiz. Enerji verimli ürün ve hizmetlerimiz müşterilerimizin elektrik gücünün yanı sıra, hidrolik ve mekanik gücü daha güvenilir, verimli, emniyetli ve sürdürülebilir şekilde yönetmelerine yardımcı olmaktadır. Bunları da, insanlara gücü daha verimli kullanabilecekleri araçlar temin ederek, şirketlerin daha sürdürülebilir şekilde iş yapmalarına yardım ederek ve Eaton’daki her çalışanımızı işimiz, toplumlarımız ve dünya üzerinde bırakabileceğimiz etki hakkında farklı düşünmeye teşvik ederek başarıyoruz.
EATON 109720 3x40A 25kA Kompakt Şalter için 1 değerlendirme
Değerlendirme yazabilmek için oturum açmalısınız.
depoda –
Teşekkürler